Changing IM 151-7 CPU (6ES7 151-7Ax00..) to IM 151-7 CPU (6ES7 151-7AA10-0AB0)
11-2
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
SFC 13 ”DPNRM_DG”
This SFC always runs “quasi-synchronously” when called in OB 82.
It always runs asynchronously on the IM 151-7 CPU (6ES7 151-7AA10-0AB0).
Note
In the user program, all that should take place is that the task should be called in
the OB 82. The evaluation of the data, which should take into account the BUSY
bits and the acknowledgement in the RET_VAL, should take place in the cyclic
program.
Tip:
We recommend using the SFB 54 instead of the SFC 13 with the IM 151-7 CPU
(6ES7 151-7AA10-0AB0).
SFC 20 ”BLKMOV”
Previously this SFC could also be used to copy data from a non-process-related
DB.
The SFC 20 no longer has this functionality. The SFC 83 ”READ_DBL” must now
be used for this purpose.
SFC 54 ”RD_DPARM”
This SFC is no longer available. The asynchronous SFC 102 RD_DPARA must
be used instead.
SFCs which may give different results
If you only use logical addressing in your user program, you can ignore the
following points.
If you use address conversions in the user program (SFC 5 ”GADR_LGC”, SFC 49
”LGC_GADR”), you must check the slot assignment and logical start address
assignment for DP slaves.
The diagnostic address of the DP slave is now always assigned to slot 0
(station proxy).
The DP slave is integrated in STEP 7:
The interface module (slot 2) may have its own address
(e.g. IM 151-7 CPU as I slave).