Addressing
3-3
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
Address Assignment
Depending on the slot, 1 byte is reserved for digital I/Os and 16 bytes are reserved
for analog I/Os in the address areas of the IM 151/7 CPU for each I/O module
(maximum of 63).
The table below indicates the default address assignment for analog and digital
modules per slot. The address areas of the I/O modules are ”visible” only to an
IM 151-7 CPU in the ET 200S, not to the associated DP master. The DP master
has no direct access to the I/O modules.
Table 3-1 Addresses of the ET 200S I/O modules
Reserved
Slot Number
Address Area
1 2 3 4 5 6 7 8 ... 66
Digital
modules, motor
starters
*
- 1 2 3 4 ... 62
Analog
modules,
process-related
modules
151-7 CPU*
IM 151-7 CPU
151-7 CPU*
- 272 to
287
288 to
303
304 to
319
320 to
335
... 1248 to
1263
Power modules
IM
I
IM
256 272 288 304 320 1248
* With X1 as the MPI-/DP interface and X2 as the DP master interface
The unassigned addresses in the range 64 to 127 are in the process image in
default addressing and can be used any way you choose in the user program. If 2
bits in a byte are already occupied by a digital module, the remaining 6 bits cannot
be used as you choose (e.g. the bits 1.4 to 1.7 in Figure 3-3).
You can use the bytes in the address areas that are not used by modules in any
way you choose in your user program. In the configuration in Figure 3-3, for
example, bytes 2 and 3 can be used as you choose.