Commissioning and Diagnostics
7-22
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
7.6.6 Interrupt status
Definition
The interrupt status of the station diagnosis provides detailed information about a
DP slave. The station diagnosis begins at byte y and can comprise max. 20 bytes.
Structure
The following figure shows the structure and content of the bytes for a configured
address area of the intermediate memory.
Byte y+1
01
H
: Code for diagnostic interrupt
02
H
: Code for process interrupt
Byte y+4
Byte y
Length of the interrupt status, including byte y
(max. 20 bytes)
Code for the station diagnosis
00
Byte y+2
Slot no.:
2 = CPU
4 ... 35 = No. of configured
address area of
intermediate memory
Diagnostic and interrupt data
Byte y+3
000000
to
Byte y+7
For
diagnostic
interrupt
only
70654 13 2 Bit no.
70654 13 2 Bit no.
7065 4 13 2 Bit no.
00 = No further information
on diagnostic status
01 = Incoming diagnosis
(at least 1 fault
exists)
10 = Outgoing diagnosis
11 = Outgoing diagnosis, but
another fault exists
.
.
.
Byte z
Example of byte y+2:
CPU = 02
H
1st address area = 04
H
2nd address area = 05
H
etc.
Figure 7-6 Structure of the interrupt status