Commissioning and Diagnostics
7-27
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
7.7.2 Structure and content of the diagnostic data bytes 0 to 7
The structure and content of the individual bytes of the diagnostic data are
described below. The following generally applies: If an error occurs, the
corresponding bit is set to ”1”.
Bytes 0 and 1
Byte 0
76 0
Module fault
External fault
Channel fault exists
54321
Byte 1
76 054321
Module class (see Table 7-13)
00
0
00
0
0
10
Channel information available
Figure 7-10 Bytes 0 and 1 of the diagnostic data
Module classes
The table below contains the identifiers for the module classes (bits 0 to 3 in
byte 1).
Table 7-13 Identifiers of the module classes
Identifier
Module class
0101 Analog module
0110 CPU
1000 Function module
1001 Digital module (I/O with limited address area)
1100 CP
1101 PS
Bytes 2 and 3
These bytes are not used.