Getting Started
2-7
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
2.4 4ht step: Configuring the IM 151-7 CPU for stand-alone
operation (MPI)
Se-
quence
Action Result
1 Does the wizard for a new project appear in the
SIMATIC Manager?
If yes: Close the wizard because the
IM 151-7 CPU is not supported by the
project wizard.
If no: Proceed to point 2
2 In the main menu of the SIMATIC Manager,
navigate to File and select the menu item New.
Enter Getting Started as the project name and
click on the OK button.
A new project is created and opened.
3 Navigate to Insert and select the menu item
Station.
In the list, click on: SIMATIC 300 Station.
4 Rename this station to ET 200S SIMATIC 300(1) is renamed to ET 200S”.
5 In the SIMATIC Manager, navigate to ET 200S
Station.
Double-click on the Hardware symbol in the
right-hand part of the window to open the Editor
used to edit the hardware configuration.
6 If no catalog is shown in the right-hand part of
the window, activate it by selecting the
command Catalog in the View menu.
In the catalog, navigate through PROFIBUS-DP
to ET 200S.
Drag the IM 151-7 CPU whose order number
matches the order number on your
IM 151-7 CPU, and drop it into the top left-hand
window. By default, the IM 151-7 CPU is
integrated as a stand-alone CPU (MPI/not
networked).
Note:
You can find out the order number in the
catalog by clicking on an IM 151-7 CPU in the
catalog. The order number of this
IM 151-7 CPU then appears in the field below
the catalog.
Vista de pagina 32