A5E00058783-04
Availability of the S7 connections
The table below shows the S7 connections available on the IM 151-7 CPU.
Table 8-13 Availability of the S7 connections
Parameters
IM 151-7 CPU
Total number of S7 connections 12
Reserved for PD communication 1 to 11
Default: 1
Reserved for OP communication 1 to 11
Default: 1
Reserved for S7 basic communication 0 to 10
Default: 0
Free S7 connections All unreserved S7 connections are shown
as free connections.
Example of an IM 151-7 CPU
The IM 151-7 CPU makes 12 S7 connections available:
Reserve 2 S7 connections for PD communication.
Reserve 3 S7 connections for OP communication.
Reserve 1 S7 connection for S7 basic communication.
There remain 6 S7 connections for other communication utilities, such as S7
communication, OP communication, etc.