IP 240 Positioning
Technical Specifications
Block number : 168
Block name : STEU.
POS
AG Library number
Call length/
Block length
CPU
Processing time
1
Function 1 20 21 22 3 41/42 5 6
S5-115U P71200-S 5168-D-2 5 words/
830 words
941-7UA...
942-7UA...
943-7UA...
944-7UA...
approx. 21 22 22 22.5 21 28.5 25.5 25 ms
approx. 9.6 8.4 9.0 10.5 8.8 10.5 9.6 10 ms
approx. 6.6 6.0 6.2 7.6 6.2 6.8 6.6 7.4 ms
approx. 2.3 2.0 2.9 2.8 1.9 2.3 2.0 2.7 ms
approx. 2.3 2.0 2.9 2.8 1.9 2.3 2.0 2.7 ms
941-7UB...
942-7UB...
943-7UB...
944-7UB...
approx.6.4 6.0 6.2 7.4 6.0 6.6 6.4 7.4 ms
S5-135U/
S5-155U
P71200-S 9168-D-2 5 words/
833 words
922 ab A9
928-3UA...
approx. 4.3 4.8 4.8 5.3 5.0 6.2 5.3 5.8 ms
approx. 2.5 2.6 2.8 3.4 2.9 4.0 3.1 3.7 ms
928-3UB... approx. 2.4 2.1 2.1 3.0 2.2 3.0 2.2 3.0 ms
S5-150U P71200-S 4168-D-1 5 words/
805 words
approx. 1.0 0.8 1.0 1.7 1.0 1.7 1.0 1.8 ms
S5-155U P71200-S 6168-B-1 5 words/
947 words
946-3UA.../
947-3UA...
approx. 1.0 0.9 1.8 2.5 1.0 1.6 1.4 1.7 ms
Nesting depth : 0
Subordinate blocks : S5-115U OB160 (only CPUs to -7UB...)
S5-135U OB122
S5-155U OB91, OB122
Reservations in data area : Data block specified in the DBNR parameter. The number of data words depends
on the number of positions stored.
Flags : MB 240 to 255
System area : S5-135U BS 60 to 63
: S5-150U BS 150 to 153
: S5-155U BS 60 to 63
System operations : yes
1
The execution times shown above apply for an FB call following an IP 240 firmware cycle without data interchange.
Note that
• when data are read out from the IP, no further data interchange is possible in that firmware cycle.
• when new data are written to the IP, no further data interchange is possible in that firmware cycle, nor in the
next cycle.
EWA 4NEB 811 6120-02a
10-93