IP 240 Module Description and Accessories
2 Module Description and Accessories
2.1 General Technical Specifications
Temperature
Operation 0 to +55 °C
(Intake air tem-
perature,
measured at the
bottom of the
module)
Storage/shipping - 25 to + 70 °C
Temperature change
- Operation 10 °C/h max.
- Storage/shipping 20 °C/h max.
Relative humidity to DIN 40040
15 to 95% (indoors)
noncondensing
Atmospheric pressure
- Operation 860 to 1060 hPa
- Storage/shipping 660 to 1060 hPa
Damped oscillatory
wave test (1 MHz) to IEC 255-4
Digital-
inputs and outputs 1 kV
Static electricity to IEC 801-2
(discharge on all
parts accessible to
the user during
normal operation)
Test voltage 3 kV
Radiated electro-
magnetic field test to IEC 801-3
Test field strength
3 V/m
Fast-transient
burst test to IEC 801-4
Digital-
inputs and outputs 1 kV
Vibration to IEC 68-2-6
- Tested with 10 to 57 Hz,
(constant ampli-
tude 0.15 mm)
57 to 150 Hz,
(constant acceler-
ation 2 g)
Shock IEC 68-2-27
-Tested with 12 shocks
(semisinusiodal
15 g/11 ms)
Free Fall IEC 68-2-32
- Tested with Height of fall 1 m
Degree of protection to IEC 529
- Implementation IP 20
- Class I to IEC 536
Insulation rating
for the digital outputs to VDE 0160
- Nominal insulation
voltage between
electrically
independent circuits
and
circuits connected
to central ground 30 V DC
Test voltage sinusoidal, 50 Hz
at a rate voltage U
e
500 V
of the AC or DC
circuit of
U
e
=0 to 50 V
Climatic Environmental Conditions Mechanical Environmental Conditions
Specifications on IEC/VDE safety
Electromagnetic Compatibility (EMC)
Noise Immunity
EWA 4NEB 811 6120-02a
2-1