IP 240 Positioning
To compensate backlash, you can specify that the IP output is to be disabled on a approach to
position only when the direction of travel was positive (ascending actual value). If the position
was approached in a negative direction, the IP output remains set and the position is ”overrun”.
When the BEE2 range is exited, the output must be reset over the S5 CPU (via embedded
commands to the IP 240). The position must then be reselected.
With the same logic, synchronization is attained following an approach to reference point only
when the reference point was reached from a positive direction.
Actual value-dependent interrupt generation
During configuring, you specify at which points on an approach to position the IP 250 is to
generate interrupts. By reading the interrupt request bytes from the IP 240, you can react
appropriately to the cause of the interrupt.
Interrupts can be generated at the following points:
On entry into ranges BEE1, BEE2 and BEE3.
Upon unintentional exiting of range BEE3 (target range exited).
On exiting range BEE2 (reversal of direction to compensate for backlash possible).
Fig. 10-9. Actual Value-Dependent Interrupt Generation
BEE1
Target
position
BEE3BEE3
Exiting of
target range
(range BEE3)
BEE1BEE2BEE2
Actual value
Entry into
range BEE1
Entry into
range BEE3
Exiting of
target range
BEE2
Entry into
range BEE2
Direction of travel Direction of travel
All interrupts are generated only once per selected position.
Methods of synchronization
Positioning with the IP 240 is possible only following synchronization of the actual value. Three
methods of synchronization are available for this purpose.
a) Reference point approach
For reference point approach, you can calibrate the actual value to a fixed reference point in
the traverse range with the aid of the incremental encoder's zero mark signal.
To make reference point approach possible, you must connect a preliminary contact switch to
the IP 240's IN input.
b) Synchronization with an internal control bit
This method of synchronization is referred to in the following as software-controlled synchro-
nization.
Each time a set control bit is transferred, you can reset the actual value and reactivate the po-
sition last selected. Positioning then begins immediately.
EWA 4NEB 811 6120-02a
10-9