Commissioning and optimization (software)
7.2 Commissioning and optimization of the frequency converter and motor combination
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
87
Table 7-4 Settings for P0340
P0340 Meaning
0 No calculation
1 Complete parameterization
2 Calculation of the replacement circuit data
3 Calculation of V/f and the closed-loop vector control
4 Calculation of the controller settings
For complete parameterization (P0340=1), not only the motor and controller parameters are
assigned in advance but also the parameters which are related to the rated motor data
(e.g. torque limit values and reference quantities for interface signals). The List Manual
contains a full list of all parameters depending on P0340. For calculation of the motor and
controller data with P0340 there are various scenarios which can be called up as a function
of the known data.
7.2.3 Motor Data Identification
Description
The Inverter has a measuring technique which is used to determine the motor parameters:
Equivalent circuit diagram (ECD) P1900 = 2
Measures Equivalent circuit diagram
(ECD) + Magnetizing characteristic
(includes P1900 = 2)
P1900 = 3
For control-related reasons, it is essential that the motor data identification is performed.
Without performing the motor data identification it is only possible to estimate ECD data
using information from the motor rating plate. For example, the stator resistance is extremely
important for the stability of the closed-loop Vector control and for the voltage boost of the V/f
characteristic. The motor data identification routine should be executed, especially if long
feeder cables or if third-party motors are being used.
If the motor data identification routine is being started for the first time, then the following
data is determined, starting from the rating plate data (rated [nominal] data) with P1900 = 2:
ECD data
Motor cable resistance
IGBT on-state voltage and compensation of IGBT gating dead times.
The rating plate data represents the initialization values for the identification. This is the
reason that it is necessary to have the correct input from the rating plate data when
determining the data specified above.