Commissioning and optimization (software)
7.2 Commissioning and optimization of the frequency converter and motor combination
ET 200pro FC
86 Operating Instructions, 11/2007, A5E01100763B AA
STARTER projects
STARTER can be used to either create a new project or open an existing one. To create a
new project in STARTER, any of the following procedures can be used:
● Find frequency converter
● Wizard
● Select frequency converter
When an existing project is opened or a new one created, STARTER will be in offline mode.
To go online, press the
("Connect to target system") button.
Changing parameters with STARTER
Parameters can be changed online or offline (but preferably online). Parameter changes
made online are stored in the RAM of the frequency converter. Transferring from RAM to the
EEPROM can be triggered manually by pressing the
("Copy RAM to ROM") button. If the
content of the RAM and EEPROM are different when the user closes STARTER, he/she will
be asked if he/she wishes to transfer the data from the RAM to the EEPROM.
Note
The storage method can be changed by means of P0014:
• P0014=0: Parameter changes stored in RAM (default)
• P0014=1: Parameter changes stored in EEPROM.
Parameter sets that have been changed offline can be transferred to the frequency converter
using the download function
("Download project to target system").
CAUTION
Parameters for safety functions can only be changed in online mode. Parameters for safety
functions are not downloaded when parameters are downloaded using STARTER.
7.2.2 Calculating the motor and controller data
The internal motor and controller data are calculated using the parameter P0340, or
indirectly with the help of the parameter P3900 or P1910. The function of the parameter
P0340 can be used, for example, if the data of the replacement circuit or the values of the
moments of inertia are known.