Series commissioning and operation
8.1 Transfer of the frequency converter parameter assignment
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
131
8.1.6 Fault codes during upload and download
Fault codes
If a fault occurs during an automatic download procedure, the frequency converter returns to
the parameter set that was previously stored in the EEPROM and the following fault codes
are generated:
Error Cause Remedy/Test
F00061 No MMC inserted
• MMC faulty?
• Insert an MMC and attempt the upload/download
again.
F00062 MMC contents invalid
• MMC faulty?
• Parameter valid for this frequency converter?
F00063 MMC contents incompatible
• MMC faulty?
• Parameter set clone00.bin available on the MMC
• Parameter valid for this frequency converter?
F00395 Different application ID after download See below
NOTICE
Once parameters have been uploaded from and downloaded to different frequency
converters, the parameter settings must be checked.
Downloading parameters from another frequency converter may cause a fault to occur with
F00063 output, if there are parameters that cannot be downloaded (check P0949 regarding
the (first) parameter number that cannot be downloaded).
If fault code F00061 or F00063 occurs during startup, it can only be cleared by shutting
down and restarting.
Remedy for F00395
If fault F00395 occurs, the loaded parameter set must be checked and confirmed by clearing
code F00395. The procedures are different for standard and fail-safe frequency converters.
F00395 for standard frequency converter
For a frequency converter without fail-safe functions, code F00395 can be cleared by means
of:
● Setting P7844 = 0 (confirmation of parameter download) or
● Setting P7844 = 2 (rejection of parameter download)
→ The frequency converter must be commissioned.
● Fault F00395 is acknowledged automatically by both P7844 settings.