Alarm, fault, and system messages
9.5 Device diagnostics
ET 200pro FC
Operating Instructions, 11/2007, A5E01100763B AA
145
Depending on the CPU being used, other organization blocks can be integrated for
diagnostics purposes.
If an error occurs in the frequency converter, a diagnosis is reported and OB82 called. Error
code 27 is always reported. Detailed error diagnostics is only possible by reading out
parameters P0947 to P0949 with SFC59.
9.5 Device diagnostics
Parameter P8820 (1 - 31) contains information about the product version for the current
frequency converter which can be read via
STARTER
PLC using the "Read parameters" function (PROFIdrive mode)
PC on the fieldbus using the I&M0 function.
The parameter is assigned as follows:
I&M function Byte
length
Format Example Related parameter
(Index)
MANUFACTURER_ID 2 U16 42 P8820[5]
ORDER_ID 20 VS 6SL3235-0TEpp-pRB0 P8820[6-15]
SERIAL_NUMBER 16 VS 12345 P8820[16-23]
HARDWARE _REVISION 2 U16 1 P8820[24]
SOFTWARE_REVISION 4 1 Char
3 U8
V123 P8820[25-26]
REVISION_COUNTER 2 U16 0x0001 P8820[27]
PROFILE_ID 2 U16 0x3A00 P8820[28]
PROFILE_SPECIFIC_TYPE 2 U16 0x0003 P8820[29]
IM_VERSION 2 2 U8 11 P8820[30]
IM_SUPPORTED 2 U16 0x0000 P8820[31]
9.6 Fault clearance
Fault clearance depends on locating the cause of the fault exactly. Details of the possible
causes of faults and measures for eliminating them can be found in the list manual and in
STARTER (using the help function).