Appendix
A.1 Acceptance Log
ET 200pro FC
158 Operating Instructions, 11/2007, A5E01100763B AA
Function test "Safe Torque Off" (STO)
This test comprises the following steps:
Table A-4 "Safe Torque Off" function (STO)
No. Description Status
1. Initial state
Drive is "Ready to Run" (P0010 = 0)
No safety faults and alarms
r9772.0 = r9772.1 = 0 (STO de-selected and inactive)
P9659 = time intervals for the forced checking procedure correctly set
2. Operate the drive
3. Check that the expected drive operates
4. Select STO while issuing the command to operate
5. Check the following:
The drive coasts-down
The drive is braked by the mechanical brake and held if a brake is being
used
No safety faults
r9772.0 = r9772.1 = 1 (STO selected and active), r9772.14 = 1 if Safe
Brake Control is enabled
6. De-select STO
7. Check the following:
No safety faults
r9772.0 = r9772.1 = 0 (STO de-selected and inactive) , r9772.14 = 0
8. Check that the expected drive operates if so the following is tested:
That the wiring between the control unit and power module is correct
Correct assignment, drive No. – inverter power module – motor
That the hardware is correctly functioning
That the shutdown paths have been correctly wired
Correct assignment of the STO terminals on the control unit
Correct parameterization of the STO function
Routine for the forced checking procedure of the shutdown paths