Commissioning and optimization (software)
7.6 Performing a reset to factory settings
ET 200pro FC
120 Operating Instructions, 11/2007, A5E01100763B AA
7.6.1 Factory settings
Factory default settings
After the frequency converter is reset to the factory settings, it can be operated without any
additional parameterization provided the default settings of the frequency converter match
the following data of a 4-pole motor:
Default line frequency 50 Hz
Rated motor voltage P0304
Rated motor current P0305
Rated motor output P0307
Rated motor frequency P0310
Rated speed P0311
(We recommend a Siemens standard motor.)
The following conditions must also be fulfilled:
Control (ON/OFF command) through fieldbus P0700=6
Asynchronous motor P0300=1
Self-cooled motor P0335=0
Motor overload factor P0640=150 %
Setpoint input through fieldbus P1000=6
Minimum frequency P1080=0 Hz
Maximum frequency P1082=50 Hz
Ramp-up time P1120=10 s
Ramp-down time P1121=10 s
Linear V/f characteristic P1300=0
NOTICE
If the settings made go beyond the factory settings, then careful attention must be paid -
depending on the complexity of the application - to the description of special functions and
to the parameter list plus function diagrams when commissioning the frequency converter.