Commissioning and optimization (software)
7.4 Commissioning of communication between the S7 CPU and the frequency converter
ET 200pro FC
108 Operating Instructions, 11/2007, A5E01100763B AA
Error values in parameter responses
Table 7-14 Error values in parameter responses
Error
value
Meaning Remark Additional
inf.
0x00 Invalid parameter number Access to a non-existent parameter.
0x01 Parameter value cannot be
modified.
Attempt to modify a read-only
parameter.
Subindex
0x02 Low or high limit exceeded Attempted modification with value
outside limits.
Subindex
0x03 Invalid subindex Access to non-existing subindex. Subindex
0x04 No field Access with subindex to non-indexed
parameter.
0x05 Incorrect data type Attempt to modify with a value which is
incompatible with the data type of the
parameter.
0x06 Invalid "Set" action (only reset is
allowed)
Attempt to modify with a value unequal
0 in a situation where this is not
allowed.
Subindex
0x07 The descriptive element cannot be
modified.
Attempt to modify a read-only
descriptive element.
Subindex
0x09 No descriptive data Access to a non-existent description
(parameter value exists).
0x0B No priority active Attempted modification without active
priority.
0x0F No text field available Attempt to access a non-existent text
field (parameter value exists).
0x11 Request cannot be executed on
account of the operating state
Access is temporarily disabled for
unspecified reasons.
0x14 Invalid value Attempt to modify with a value which
lies within the limits, however, is
invalid for other permanently valid
reasons (parameters with permanently
defined values).
Subindex
0x15 Response too long The length of the present response
exceeds the maximum transfer length.
0x16 Invalid parameter address Invalid or unsupported value for
attribute, number of elements,
parameter number, subindex, or a
combination of these.
0x17 Invalid format Write request for an invalid or
unsupported parameter data format.
0x18 Inconsistent qty. of values Write request - The number of values
in parameter data and the number of
elements in the parameter address do
not match.
0x19 Drive object is not present Access to a drive object which is not
present.
0x20 The parameter text element cannot
be modified.
Attempt to modify a read only
parameter text element.
Subindex