Installation
4.5 Mounting the terminating module
ET 200pro FC
44 Operating Instructions, 11/2007, A5E01100763B AA
4.5 Mounting the terminating module
The ET 200pro station must be terminated with the terminating module.
Requirements
● All bus modules are mounted on the rack.
Required tools
Cross-tip screwdriver, size 2
Procedure
1. Mount the terminating module onto the rack.
2. Slide the terminating module to the left up against the last bus module.
Note
Do not screw the terminating module to the rack (2 recessed head screws at the front,
torque 1.5 Nm) until all the bus modules are mounted and screwed in place.
The terminating module is included in the scope of delivery of the interface module.