Siemens TCP/IP Ethernet Driver Help
Solution:
Verify that the Simatic STEP 7 project is not corrupt and can be successfully opened in Simatic STEP 7. If this
error continues to occur, contact Technical Support.
String conversion warning: Auto generated tag names and descriptions may not
appear as expected for device <channel.device>.
Error Type:
Warning
Possible Cause:
The unicode conversion failed.
Solution:
Verify that the STEP 7 language file exists and reflects a character set that can display the STEP 7 tags and
comment strings.
Unable to generate a tag database for device <channel.device>. Reason: The
STEP 7 project file has not been specified.
Error Type:
Warning
Possible Cause:
The STEP 7 project file has not been specified.
Solution:
Verify that the STEP 7 project file has been specified in the Tag Import tab of Device Properties.
See Also:
Tag Import
Unable to generate a tag database for device <channel.device>. Reason: The
program path has not been specified.
Error Type:
Warning
Possible Cause:
The STEP 7 program path has not been specified.
Solution:
Verify that the STEP 7 program path has been specified in the Tag Import tab of Device Properties.
See Also:
Tag Import
Unable to generate a tag database for device <device name>. Reason:
<model> devices do not support auto tag database generation.
Error Type:
Warning
Possible Cause:
The selected model does not currently support Automatic Tag Database Generation.
Solution:
Generate the tags manually.