Siemens TCP/IP Ethernet Driver Help
Array ID0_4_3
----
MD0_4_3
----
----
DB1.DBD0F_4_3
Note:
All brand and product names are trademarks, registered trademarks, or service marks of their respective
holders.
INAT OPC Server TCPIPH1 Item Syntax
The following support for the INAT OPC Server TCPIPH1 (V1.22 and up) is considered to be limited. Care must be
taken as the data type for a given S7 data type/suffix may differ from the data type for the same S7 data
type/suffix in the specified product. S7 data type and suffixes not included below are not supported by this
driver. The following information is intended to be a guideline for users that are already familiar with and/or
prefer the syntax of the specified product. For preferred item syntax, refer to Standard S7-
300/400/1200/1500 Item Syntax.
Address Syntax
Input, Output, Peripheral, Flag Memory Types
<memory type><S7 data type><address>[<suffix>]
<memory type><S7 data type><address><.string length>*
<memory type><S7 data type><address><.array size>[<suffix>]
Timer and Counter Memory Types
<memory type><address>
DB Memory Type
DB<num>.<S7 data type><address>[<suffix>]
DB<num>.<S7 data type><address><.string length>*
DB<num>.<S7 data type><address><.array size>[<suffix>]
Where <num> ranges from 1 to 65535.
*Applies to S7 data types that support string.
See Also: Examples
Memory Types
Memory Type Description Address Range Data Type Access
I
E
Inputs
Dependent on S7 Data Type
Read/Write
Q
A
Outputs Read/Write
PI
PE
Peripheral Inputs Read Only
PQ
PA
Peripheral Outputs Read/Write
M
F
Flag Memory Read/Write
DB Data Blocks Read/Write
T Timers T0-T65535 DWord, Long Read/Write
C
Z
Counters C0-C65535
Z0-Z65535
Word, Short Read/Write
See Also: Examples
S7 Data Types
The S7 data type is used to coerce the data type for a tag. It does not apply to Timers and Counters. Default data
types are shown in bold. A suffix is not required.
Data
Type
Description Address Range Data Type Suffix
Data Type w/
Suffix
X Bit X0.b-X65534.b
.b is Bit Number 0-15
Boolean
B Unsigned Byte B0-B65535 Byte, Char KF Char