Siemens TCP/IP Ethernet Driver Help
Address Descriptions
Address specifications vary depending on the model in use. Select a link from the following list to obtain
information for the model of interest.
S7-200 Address Descriptions
S7-300 Address Descriptions
S7-400 Address Descriptions
S7-1200 Address Descriptions
S7-1500 Address Descriptions
NetLink: S7-300 Address Descriptions
NetLink: S7-400 Address Descriptions
Internal Tags
S7-200 Address Descriptions
The default data types for dynamically defined tags are shown in bold.
Address Type Range Type Access
Discrete Inputs (IEC) I0.b-I65535.b
.b is Bit Number 0-7
IB0-IB65535
IW0-IW65534
ID0-ID65532
Boolean
Byte, Char, String**
Word, Short, BCD
DWord, Long, LBCD,
Float
Read/Write
Read/Write
Read/Write
Read/Write
Discrete Inputs (SIMATIC) E0.b-E65535.b
.b is Bit Number 0-7
EB0-EB65535**
EW0-EW65534
ED0-ED65532
Boolean
Byte, Char, String**
Word, Short, BCD
DWord, Long, LBCD,
Float
Read/Write
Read/Write
Read/Write
Read/Write
Note: I and E access the same memory area.
Discrete Outputs (IEC) Q0.b-Q65535.b
.b is Bit Number 0-7
QB0-QB65535
QW0-QW65534
QD0-QD65532
Boolean
Byte, Char, String**
Word, Short, BCD
DWord, Long, LBCD,
Float
Read/Write
Read/Write
Read/Write
Read/Write
Discrete Outputs (SIMATIC) A0.b-A65535.b
.b is Bit Number 0-7
AB0-AB65535
AW0-AW65534
AD0-AD65532
Boolean
Byte, Char, String**
Word, Short, BCD
DWord, Long, LBCD,
Float
Read/Write
Read/Write
Read/Write
Read/Write
Note: Q and A access the same memory area.
Analog Inputs (IEC)
AI0-AI65534***
AIW0-AIW65534
Word, Short Read Only
Analog Inputs (SIMATIC) AE0-AE65534***
AEW0-AEW65534
Word, Short Read Only
Note: AI and AE access the same memory
area.
Analog Outputs (IEC) AQ0-AQ65534***
AQW0-AQW65534
Word, Short Read/Write
Analog Outputs (SIMATIC) AA0-AA65534***
AAW0-AAW65534
Word, Short Read/Write
Note: AQ and AA access the same memory area.
Internal Memory M0.b-M65535.b
.b is Bit Number 0-7
Boolean Read/Write