ON-LINE AND OFF-LINE OPERATION UM344-2
September 1995
5
-
24
5.1.4 Quick Access Key
Operation
MXC Quick Access keys are used to view transmitter
parameters while the MXC is on-line and communicating with a
transmitter (refer to Section 2). Eight Quick Access keys are
used with the Model 344: TRANS. VAR'S., TREND, ZOOM,
and STATUS, are available with the controller ON or OFF.
CHANGE SP, CHANGE VALVE, A/M and TUNE are only
available when the controller is ON. Press a key to access live
transmitter data.
NOTE
Conserve battery power. Do not leave the MXC
in the on-line mode.
1. Establish communication with a transmitter, see Section 3.2,
and go to the On-Line Menu (adjacent).
2. Press a Quick Access key to view the desired transmitter
parameter(s) at the On-Line Menu. The following
paragraphs will describe how to view these parameters.
TRANS. VAR'S. - displays updated on-line transmitter
parameters. These parameters include the measured
variable (MV), the current output (I), the process variable
(PV) and their respective units or the Process (P), Set Point
(S) and Valve (V) controller variables.. Exit this screen by
again pressing the TRANS. VAR'S. key or pressing END.
TREND - displays the adjacent screen to select the variable
to be trended.
1) Press PREV or NEXT to toggle between Process
Variable, Measured Variable, and Valve with the
Controller “ON.”
2) Press SELECT to enter a value. Pressing END will exit
this procedure and display the On-Line Menu.
3) Type the desired sample time: range 1-300 seconds;
default is 1 second. Thirteen samples (maximum) of the
variable can be shown while sampling at the sample time
chosen.
If the sample time entered is greater than 300 seconds, a
Warning message will appear that shows the range of
values.
M: 76.534 deg F
I: 3.8377 mA
P: 63.272 deg F
END
Dev ID: 210300003C
Tag: TTC-101 ADD: 00
LOOP CAL/ CON -
END
OVRD
TEST FIG
TREND WHICH VAR?
MEASURED VARIABLE
SEL-
PREV NEXT END ECT
ENTER SAMPLING TIME
SECONDS
EN-
< END TER
WARNING: TREND TIME
MUST FALL BETWEEN
1 AND 300 SECONDS.
EXIT