CALIBRATION AND MAINTENANCE UM344-2
September 1995
4. Press CONT (F4). Screen will display:
5. Adjust the output of the millivolt source to -18.000 mV.
6. Press CONT (F4). Screen will display:
7. Press CONT (F4) to calibrate.
Press ABRT (F3) to quit without changing calibration.
8. Wide Millivolt calibration is completed.
Disconnect test equipment, reconnect wires, and install enclosure cap.
This completes the calibration checks and procedures
6.2 PREVENTIVE MAINTENANCE
Preventive maintenance consists of periodic inspection of the transmitter, cleaning the external surface of
the transmitter's enclosure, and draining condensate from conduit. Preventive maintenance should be
performed at regularly scheduled intervals.
NOTE
The electronics module contains integrated circuits that can be damaged by
improper handling. The high quality devices used contain built-in protective
circuitry, however, they can be damaged by low energy, high voltage
electrostatic discharge. Follow procedures to prevent the buildup and
discharge of electrostatic energy (see Service Kit below).
6.2.1 Tool and Equipment Requirements
The following tools and equipment are required for servicing:
Ÿ Set of Phillips, flat-blade, and Torx-Head screwdrivers.
Ÿ Service Kit containing wrist strap and conductive mat (P/N 15545-110 or equivalent) for handling
semiconductor components and circuit board assemblies.
Ÿ Digital Multimeter (DMM); see Section 6.1.1 for specifications
CONT
APPLY -18.000 mV TO
mV+ (1) TO AND mV- (3)
WITH COPPER WIRE
WARNING: BURNING
EPROM WILL CHANGE
CALIBRATION CHARAC-
TERISTICS
CONT
ABRT