UM344-2 INSTALLATION
September 1995
4
-
31
4.5 ELECTRICAL INSTALLATION
This section describes loop wiring for Point-To-Point and Multi-Drop Networks. Refer also to Section 4.6
for installations in hazardous locations. Figure 4-12 shows signal and sensor termination terminal strips in
the Transmitter’s enclosure.
The following should already have been completed:
Ÿ Selection of either analog or digital operating mode and corresponding Point-To-Point or Multi-Drop
Network; Section 4.3.3.
Ÿ Selection of a power supply; Section 4.3.4.
Ÿ Mechanical installation of Transmitter(s) installed; Section 4.4.
Ÿ Pulling of loop and sensor cables through conduit and into terminal compartment; Section 4.4.5.
Connect the transmitter to the loop as follows.
1. Access transmitter signal terminals by unscrewing the short enclosure cap.
2. As shown in Figure 4-12, there are two terminal strips:
Upper Terminal Strip
SIGNAL (+) and SIGNAL (-): Transmitter Network Connections
TEST (+) and TEST (-): Analog test (milliammeter) connections
Lower Terminal Strip
#1: RTD (+) or OHM (+); TC (+) or mV (+) sensor connections
#2: RTDI sensor connection
#3: RTD (-) or OHM (-); TC (-) or mV (-) sensor connections
3. Determine method of connection to transmitter signal (loop) terminals.
Strip loop cable and conductors. Install ring tongue or spring spade terminals for #6 screws and the
cable conductor gauge. If terminals will not be used, tin conductor ends and form a loop.