UM344-2 ON-LINE AND OFF-LINE OPERATION
August 1995
B. Change SET POINT
1. The Controller must be in the AUTO control mode to
change the SET POINT; if not, place the Controller
in the AUTO control mode.
2. Press and hold, for a minimum of 5 seconds, the
ZERO pushbutton, then release the button.
The "SP" and "PB" annunciators shall be lit and the
"PV" annunciator shall be extinguished.
The displayed number is the active SET POINT
value.
3. Select new SET POINT. Note the following.
• Cycling (pressing and releasing in less than 1
second) the ZERO or FULLSCALE pushbutton
respectively decrements or increments the SET
POINT in 0.01% increments of span.
• Pressing and holding either pushbutton, for more
than 1 second, initiates a special acceleration
algorithm whereby the SET POINT changes in
greater and greater increments until limiting
occurs.
• The new SET POINT value is changed in RAM
only and not yet stored permanently in memory.
If the Pushbutton Mode times-out before
storage is accomplished, the Controller will
operate with the new SET POINT; however, the
new value will be lost after a power-down or
Master Reset.
C. Store New SET POINT to Memory (new Power-Up
Setpoint Valve in Setpoint Track & Hold Block)
1. Simultaneously press and release both pushbuttons to
store new SET POINT.
After SET POINT storage, the Controller exits the
Pushbutton Mode and returns to normal operation.
D. Change VALVE