UM344-2 ON-LINE AND OFF-LINE OPERATION
August 1995
5.1.3.1 Display Functions The numerals displayed on the Digital Meter represent the value
of the PROCESS VARIABLE (PV) when the “PV”
annunciator is lit; see Figure 5-1. The units associated with PV
are chosen during transmitter configuration of the OPERATOR
DISPLAY BLOCK. Refer to section 5.1.1.2. There are three
OUTPUT DISPLAY CODE choices listed in Table 5.1 that
describe what information is displayed and how it will be
annunciated.
The VALVE (V) is always displayed as a percentage of
controller output and the “V” and “%” annunciators will be lit.
The SETPOINT (SP) is displayed in the same units as the
PROCESS VARIABLE (PV). When the controller is ON
depressing the FULL SCALE pushbutton will toggle the display
between “PV” and “V”. The ZERO pushbutton will toggle the
display between “PV” and “SP”.
TABLE 5.1 Output Display Code Choices
OUTPUT DISPLAY
CODE
LIT ANNUN. PV UNITS
0 (Percent) % Percent of full span (0 to 100)
1 (Process Variable) ENG Engineering Units (e.g., CEL, FAHR)
2 (Measured Variable) None CEL, OHMS, MV, KELV, RANK, FAHR
PV
SP
V
A M
PB AL % ENG
Auto/Manual
Displayed
Displayed
Variable
Indicator
PB
Status
Alarm
Status
Display
Code
FIGURE 5-1 Model 344 Digital Meter