Using the COM5434 Configurator
5-30
SIMATIC 505 PROFIBUS-FMS CP User Manual
5.10 Configuring Send-Receive Jobs
Before
you can configure a Send-Receive job, you must have defined an FDL
connection between the local FMS CP module and the remote device (see
Section 5.7). The FMS CP module supports 48 communication jobs, which
may be a combination of FMS and Send-Receive jobs. Click on Send-Receive
Jobs on the configuration tree to see the number of communication jobs
available, as shown in Figure 5-22.
For more detail on these jobs, see Section 4.4.
✂
File Edit Transfer Options Diagnostics Help
Untitled
– COM5434
Configured
Fieldbus Data Link (FDL) protocol jobs
Module Local Configuration
FMS Data T
ypes
FMS
FDL
FMS
P–P
S–R
DTs
Peerlink II Services
FMS V
ariables
<no description>
FMS Connections
Maximum Comm. Jobs:
Send-Receive Jobs:
48
0
Click here.
FDL Connections
Communication Jobs
Comm. Jobs A
vailable: 48
FMS Jobs
Send-Receive Jobs
Figure 5-22 Send-Receive
Jobs
Maximum Communication Jobs This
field displays the total number of
communication jobs supported by the FMS CP module.
Send-Receive Jobs This
field displays the number of Send-Receive jobs that
have been defined for the FMS CP module.
Communication Jobs Available This
field displays the total number of
unused communication jobs.
Send-Receive Jobs