Configuration Examples
6-14
SIMATIC 505 PROFIBUS-FMS CP User Manual
6.3 Example of a Send-Receive Job
Figure 6-1
1
shows the flow of data during Send-Receive jobs configured
between Station 1 (FMS CP) and Station 5 (FMS CP) on the example
network. Station 1 sends the data. Station 5 receives the data from
Station 1.
Station 1 Station 5
Data
from memory
Send (data only)
Acknowledge
Job: Receive
Data to memory
Data Flow
Note:
Both programmable logic controllers must have RLL code to allow data to be transferred.
FMS CP
FMS CP
CPU
CPU
Figure 6-11 Send-Receive
Job Data Flow Example
Using the COM5434 Configurator
, configure the Send and Receive jobs
between Station 1 and Station 5 by completing the following tasks:
Create and name the configuration file for Station 1.
Define the Module Local Configuration for Station 1.
Define an FDL connection for Station 1.
Configure the Send job for Station 1.
Save and download the configuration file to the FMS CP module at
Station 1.
THEN...
Create and name the configuration file for Station 5.
Define the Module Local Configuration for Station 5.
Define an FDL connection for Station 5 using the same addressing as
the connection created for Station 1.
Configure the Receive job for Station 5.
Save and download the configuration file to the FMS CP module at
Station 5.
These tasks are described in detail on the following pages.
Configuration T
asks
for a Send-Receive
Job