Connecting the Network
3-10
SIMATIC 505 PROFIBUS-FMS CP User Manual
Installing PROFIBUS Cables (continued)
The
device at each extreme end of a PROFIBUS cable must be terminated
and biased; any connections made between segment ends must not be
terminated or biased. See Figure 3-5.
N
= PROFIBUS-FMS station
T
ermination and bias required.
Segment end must be
terminated and biased.
NNN N
Controller with
PROFIBUS-FMS
CP module
Figure 3-5 Terminate
the Network at the Endpoints
Siemens PROFIBUS connectors have selectable termination and bias built
in. The connectors are designed to handle baud rates from 9600 baud to
12 Mbaud and have an external switch (see Figure 3-6). Y
ou set the
selection switch to the On position to enable termination and bias, or Off to
disable termination and bias.
9-pin
D-shell
connector
External
termination
switch
ON
OFF
Figure 3-6 Siemens
Connector
, Exter
nal T
er
mination Switch
Ter
mination and
Bias
Using a T
ermination
Selection Switch