Configuration Examples
6-6
SIMATIC 505 PROFIBUS-FMS CP User Manual
Example of an FMS Read Job (continued)
Next,
you must define the Module Local Configuration of the FMS CP
module for Station 1.
1.
Click on the Module Local Configuration icon.
2.
Complete the fields listed below (and shown in Figure 6-5) to define the
Module Local Configuration:
Local Station Address: 1
Highest Station Address: 15
Bus Parameter Profile: FMS-DP Universal
Baud Rate: 1.5 MBaud
# of Masters (holds token): 6
# of Slaves (no token): 0
File Edit Transfer Options Diagnostics Help
Untitled
– COM5434
This
module’
s FMS PROFIBUS communication parameters
FMS Connections
FDL Connections
Communication Jobs
FMS Jobs
Send-Receive Jobs
FMS Data T
ypes
FMS
FDL
FMS
P–P
S–R
DTs
Peerlink II Services
FMS V
ariables
File_A
Module Local Configuration
Local Station Address:
Slot T
ime (T
slot):
Max. Sta. Delay (Max_T
sdr):
3000
980
1
Highest Station Address:
15
Bus Parameter Profile:
FMS-DP Universal
Baud Rate:
1.5 MBaud
# of Masters (holds token):
6
# of Slaves (no token):
0
Min. Sta. Delay (Min_T
sdr):
Setup Time (T
set):
150
240
Quiet T
ime (Tqui):
Gap Factor:
0
50
Retry Limit:
T
oken Rotation (Ttr):
1
45000
Click here.
Enter parameters
here.
Edit
Figure 6-5 Module
Local Configuration Example
Defining the
Module Local
Configuration for
Station 1