Troubleshooting
B-7
SIMATIC 505 PROFIBUS-FMS CP User Manual
B.3 CP-to-Controller Status Codes
T
able B-5
CP-to-Attached
Contr
oller Err
or Codes for FMS and Send-Receive Jobs
Status
Code (Hex)
Description
80xx xx is task code error response from attached PLC; see PLC documentation. These errors
usually indicate a problem in accessing data in the attached PLC caused by a firmware error in
the CP rather than a user error.
9000 Invalid request to PLC; a firmware error in the CP rather than a user error.
9001 Memory type request from PLC is not defined for any 505 PLC. The Configurator guards
against the use of undefined data types when configuring communications between 505 PLCs,
so this should not occur. If the accessed plcTT type is unsupported or not configured in the
attached PLC, error code 9003 occurs (see below).
9002 Reserved for invalid request for PLC mode. Currently, CP does not produce this error.
9003 Memory type requested from PLC is not supported or not configured. For example, the 560
does not support loop data types. It also occurs if the requested data type is not configured in
the PLC (e.g., unconfigured analog alarm data types). Access of data types undefined for any
505 PLC results in error 9001.
9004 Starting memory address accessed in PLC is invalid. This occurs if memory type is defined,
supported, and configured, but the starting address is out of range for the data type. For
example, if the starting address is V27000 and only 52K bytes of V-memory are configured
(allowing a maximum V
-address of 26624), then this error occurs. If you reconfigured the PLC
memory after installing and initializing the CP module, reset the CP module so that it can read
the new memory configuration in the PLC.
9005 Memory type cannot be written since it is read-only.
9006 PLC communication time-out. Due to extremely heavy load on the PLC or CP, the data access
to the PLC took longer than expected. This error may also occur if the CP resides in a remote
base and the I/O cable becomes disconnected. If this error occurs, retry the job.
9007 Starting memory address OK, but the number of items requested is causing invalid memory
access. For example, this error ocuurs if 2000 words of V-memory starting at V26000 are
requested but only 52K bytes of V-memory are configured (V26624 is highest configured
address). If you reconfigured PLC memory after installing and initializing the CP module, reset
the CP module so that it can read the new memory configuration in the PLC.
9008 Slot into which CP module is placed is not configured. This error does not explicitly appear for
any job. It may be indicated on the job diagnostic display by the message “Waiting for WY bit to
trigger Job”, with a job status D000, even when the PLC is setting the WY bit. If the base is not
configured, the module is unable to detect the WY Job Start Bits required for the jobs.