Installing the Module
2-4
SIMATIC 505 PROFIBUS-FMS CP User Manual
2.2 Setting the Baud Rate for the RS-232 Port
A
header labeled E1 is located on the module, as shown in Figure 2-2. The
header determines the baud rate for the RS-232 port, and the jumper must
be set before the module is installed in the base.
Bezel
19,200
38,400
E1
)–
)–
Jumper
set on header E1 pins
at 38,400 baud.
Figure 2-2 Location
of Header E1
The RS-232 port can be set at 9600 baud (no jumper), 19,200 baud, or
38,400 baud (as shown in Figure 2-2). The default setting of Header E1, as
shipped, is 38,400 baud. T
o set the RS-232 port at 9600 baud, the jumper
must not connect two header pins. However
, in order not to lose the jumper
,
the jumper should be stored on the module by hanging it on one pin only (as
shown in Figure 2-3).
Bezel
Jumper
shown unplugged from E1
header pins. For convenient storage,
position the jumper on
one
E1 pin only
.
19,200
38,400
E1
)–
)–
Figure 2-3 Jumper
Storage at 9600 Baud
Header E2 is shipped without a jumper
, and is for factory use only. Do not
alter the state of Header E2 unless instructed to do so by a Siemens
T
echnical Support technician.
Setting the Jumper
on Header E1
Header E2