Connecting the Network
3-8
SIMATIC 505 PROFIBUS-FMS CP User Manual
Installing PROFIBUS Cables (continued)
T
able 3-1
lists the PROFIBUS EN 50 170 cable line specifications.
T
able 3-1
PROFIBUS Cable Specifications
Feature Specification
Impedance 135 Ohm to 165 Ohm
(3 MHz to 20 MHz)
Capacitance
9.1 pF/ft. (<30 nF/km)
Resistance
33.5
/1000 ft.
(<1
10 Ohm/km)
Attenuation
0.27 dB/100 ft.
(0.9 dB/100 m (f=200kHz))
Conductor Area
20 A
WG to 22 AWG
(0.3 mm
2
to 0.5 mm
2
)
Cable Diameter
0.315 in.
0.02 in.
(8 mm
0.5 mm)
Up
to 10 bus segments can be connected in series. Line length limits are
determined by baud rate. The distance between the two most widely
separated stations must not exceed the values shown in T
able 3-2. Use
repeaters between each cable segment. (For fiber
-optic cable line length
limits, consult the newest edition of Siemens’
SIMA
TIC NET Industrial
Communications Networks, Catalog IK 10
.)
T
able 3-2
PROFIBUS Line Length Limits
Baud Rate
Maximum Segment
Length
Maximum Installation
Length
9.6
to 93.75 KBaud
3,930 ft. (1,200 m)
39,300 ft. (12,000 m)
187.5 KBaud
3,280 ft. (1,000 m)
32,800 ft. (10,000 m)
500 KBaud
1,310 ft. (400 m)
13,100 ft. (4,000 m)
1.5 MBaud
660 ft. (200 m)
6,600 ft. (2,000 m)
3 Mbaud to 12 MBaud
330 ft. (100 m)
3,300 ft. (1,000 m)
PROFIBUS
Cable
Specifications
PROFIBUS Line
Length Limits
Vista de pagina 45