
KINCO
70
0810H Communication write-in selection Communication write in disabled: 0 (default),
Communication write in enabled: 1.
In the setting mode
0811H Temperature unit display selection
o
C/linear input (default): 1 ,
o
F : 0. in the setting
mode
0812H Decimal point position selection Except for the thermocouple B, S, R type, all the
other thermocouple type are valid. (0 or 1).
In the running mode
0813H AT setting OFF: 0 (default), ON : 1.
In the adjusting mode
0814H Control RUN/STOP setting 0: STOP, 1: RUN (default).
In the running mode
0815H
STOP setting for PID program control
0: RUN (default), 1: STOP.
In the running mode
0816H
Temporarily STOP for PID program control
0: RUN (default), 1: Temporarily STOP.
In the running mode
0817H Valve feedback setting status 0: w/o feedback (default), 1: feedback function.
0818H Auto-tuning valve feedback status 0: Stop AT (default), 1: Start AT
3. Communication Parameters List
z Communication protocol: Modbus (ASCII); Available communication address: 1 to 255, 0
is broadcast address
z Function code: 03H: read the contents of register (Max. 3 words).
06H: write 1 (one) word into register.
Cable Diagram
DVP RS485-2 communication cable
Comentarios a estos manuales