Input bit (read only) 1X1-65535 ------ DDDDD
Input Register (read only) ------ 3X1-65535 DDDDD
Output Register ------ 4X1-65535 DDDDD
Note
Mapping of address (same as *10 relationships):
2-01 is to 4X2010
3-02 is to 4X3020
So address 4X1300 is to 1-30 as following picture, here is double word address. To get more
information, please refer to danfoss manual.
In addition, to get mapping address of startup, you should set bit of 3, 4, 5, 6,7,11 coil on:
0x047C=0000 0100 0111 1100
Set 0X 3, 0X 4, 0X 5, 0X 6, 0X 7, 0X 11 all to “1” (if random one of these registers is “0”,
Frequency Converter will stop.
loop 0 1
01 Preset reference value LSB
02 Preset reference value MSB
03 DC brake Do not DC brake
04 Inertial stop Do not Inertial stop
05 Quickly stop Do not Quickly stop
06 locking frequency Do not locking frequency
07 Acc/Dec stop start
08 Do not reset reset
09 Do not inching inching
10 Acc/Dec 1 Acc/Dec 2
11 valid data invalid data
12 Relay 1 close Relay 1 open
13 Relay 2 close Relay 2 open
14 Set LSB
15 Set MSB
16 Do not reverse reverse
Transducer controller word (FC structure)