4729H AT Setting
OFF: 0 (default), ON: 1. in the adjusting mode
4733H CT monitor value
Unit is 0.1A. in the running mode
DTB9696VR:Address and Content of Word Register (corresponds to 4X in the HMI)
Address Content Explanation
1000H Process value (PV) Measuring unit is 0.1, updated one time in 0.4 second
1001H Set point (SV) Unit is 0.1,
o
C or
o
F
1002H Upper-limit of temperature range
The data content should not be higher than the
temperature range. In the setting mode
1003H Lower-limit of temperature range
The data content should not be lower than the
temperature range. In the setting mode
1004H Input temperature sensor type
Please refer to the contents of the “Temperature Sensor
Type and Temperature Range” for detail. In the setting
mode
1005H Control method
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID grogram
control. In the setting mode
1006H Heating/Cooling control selection
0: Heating, 1: Cooling, 2: Heating/Cooling, 3:
Cooling/Heating. In the setting mode
1007H
1st group of Heating/Cooling
control cycle
0 ~ 99, 0:0.5 sec. in the adjusting mode
or
1008H
2nd group of Heating/Cooling
control cycle
0 ~ 99, 0:0.5 sec. in the adjusting mode
1009H PB Proportional band
0.1 ~ 999.9. in the adjusting mode
100AH Ti Integral time
0~9999. in the adjusting mode
100BH Td Derivative time
0~9999. in the adjusting mode
100CH Integration default
0 ~ 100%, unit is 0.1%. in the adjusting mode
100DH
Proportional control offset error
value, when Ti = 0
0 ~ 100%, unit is 0.1%. in the adjusting mode
100EH
The setting of COEF when Dual
Loop output control are used
0.01 ~ 99.99, unit is 0.01 (setting when it is under the
control of PID ) in the adjusting mode