KINCO
114
Series CPU Link Module Driver
KDN-K3 KDN-K304-14AR RS232 on the CPU unit KDN-K3
System configuration
Series CPU Link Module COMM Type Parameter Cable
KDN-K3 K304-14AR
RS232 on the CPU unit
RS232 Setting Your owner cable
Supported Device
KDN-K3
Device Bit Address Word Address Format Notes
Discrete inputs and image Relay I0.0-7.7 ------ D.O
Discrete outputs and image Relay Q0.0-7.7 ------ D.O
Internal memory Relay M0.0-31.7 ------ DD.O
Analog inputs ------ AIW0-30 DD
Analog outputs ------ AQW0-30 DD
Internal register ------ VW0-4094 DDDD
Internal register(double word) ------ VD0-4092 DDDD
Note:
1) AIW, AQW, VW, VD address must be an even number.
2) AIW and I device read only.
3) The single floating VR of PLC corresponds with the VD of the Ev5000 (choose single
floating).
Communication Setting
KDN-K3 RS232 communication