Passive Components for Electrical Networks
4-8
SIMATIC NET Tw isted-Pair and Fiber-Optic Networks
C79000-G8976-C125-02
Notes on Installation
The maximum total length of a segment is 100 m. To obtain the best transmission
characteristics, the segment should consist of one single section of cable. In
special situations (for example when passing through two closets), the segment
can consist of up to three separate sections of cable.
The excellent transmission characteristics of the entire system can be guaranteed
only when SIEMENS Industrial Ethernet network components are used exclusively.
Assembling Cables with Twisted-Pair Sub-D Connectors
When assembling Industrial Twisted Pair cables yourself, make sure that you only
combine the Industrial Twisted Pair standard cable 2x2 with the SIMATIC NET
Industrial T wisted Pair sub-D connector for assembly on site. The dimensions of
these two components match each other.
Do Not Connect to FC Outlet RJ-45
The Industrial Twisted Pair standard cable 2x2 is not suitable for connection to the
FC Outlet RJ-45 due to its diameter. Use FastConnect (FC) twisted-pair cables for
connection to the FC Outlet RJ-45.
Versions Available
The two-pair standard cable is available as a preassembled cable with 9-pin or
15-pin sub-D connectors or can be ordered without connectors in meters.
The following preassembled cables use Industrial Twisted Pair standard cable:
S ITP standard cable 9/15
S ITP XP standard cable 9/9
S ITP XP standard cable 15/15