Guidelines for Installing Networked Automation Systems in Buildings
7-23
SIMATIC NET Twisted-Pair and Fiber-Optic Networks
C79000-G8976-C125-02
7.5 Mechanical Protection of Bus Cables
Protection of Electrical and Optical Bus Cables
Mechanical protection is required to protect bus cables from breaks or mechanical
damage.
Note
The guidelines for mechanical protection apply both to electrical and optical
cables.
Measures for Mechanical Protection
The following measures are recommended to protect bus cables from physical
damage:
S When cable cannot be installed on a cable rack or similar construction, it should
be installed in a conduit (for example PG 11-16).
S In areas where the cable is subject to mechanical stress, install the cable in a
heavy-gauge aluminum conduit or in a heavy-gauge plastic conduit (see Figure
7-5)
S When 90° bends are necessary and at the junctions between buildings (for
example expansion joints), a break in the conduit is acceptable only when there
is no likelihood of damage to the cable, for example due to falling objects (see
Figure 7-6).
S In areas where the cable is likely to be walked on or driven over, the cable must
be protected from damage by a closed heavy-gauge aluminum or steel conduit.
As an alternative, the cable can be laid in a metal cable gutter.
Figure 7-5 Mechanical Protection of the Bus Cable