Guidelines for Installing Networked Automation Systems in Buildings
7-30
SIMATIC NET Twisted-Pair and Fiber-Optic Networks
C79000-G8976-C125-02
Fitting the Connector
1. Remove approximately 30 mm of the outer sheath from the braided shield.
30
2. Cut the braided shield approximately 10 mm from the edge of the outer sheath
and
pull off the loose shield.
10
3. Turn back the braided shield over the outer sheath.
Unwind the aluminum foil shield up to a point approximately 15 mm from the
folded back braided shield and cut off the unwound material.
Remove the plastic foil and blind elements.
Remove approximately 5 mm of the insulation from the conductors.
5
10 15
4. Wrap copper band around the braided shield