Guidelines for Installing Networked Automation Systems in Buildings
7-33
SIMATIC NET Twisted-Pair and Fiber-Optic Networks
C79000-G8976-C125-02
Fitting Connectors
1. Remove approximately 35 mm of the outer sheath from the braided screen.
35
2. Cut the braided shield approximately 10 mm from the edge of the outer sheath
and
pull off the loose shield.
Shorten the white-blue pair by approximately 3 mm to 32 mm
(to introduce the cable as shown in Figure 7-10).
white/blue
white/orange
10
32
3. - Fold back the braided shield over the outer sheath.
– Unwind the aluminum foil shield leaving approximately 15 mm (shorter pair)
or approximately 18 mm (longer pair) to the folded back braided shield and
cut off the unwound shield.
– Remove the plastic foil and blind element.
– Remove approximately 5 mm of the insulation from the conductors.
white/blue
white/orange
5
15
18
12
4. Wrap copper band around the braided shield