Configuring Networks
3-25
SIMATIC NET Twisted-Pair and Fiber-Optic Networks
C79000-G8976-C125-02
3.4.2 ESM Bus Structure
100 Mbps Switched LAN with a Bus Structure
The Industrial Ethernet ESMs allow the implementation of 100 Mbps switched
LANs with a bus structure. The maximum distance between two ESMs must not
exceed 100 m. You can cascade the modules to form a bus using any TP port. Up
to a maximum of 50 ESMs can be cascaded.
2
ESM ESM ITP 80ESM ESM ITP 80
ESM
22
34
4
4
S7-400
S7-400
S7-300
PC
2 ITP XP Standard Cable 9/9
3 TP Cord 9/RJ45
4 ITP Standard Cable 9/15
2
Figure 3-8 Bus with ESMs
3.4.3 Redundant Ring Structure with ESMs
Redundant Electrical Ring
With the aid of an ESM functioning as the redundancy manager (RM), both ends of
an electrical bus made up of ESMs can be closed to form a redundant electrical
ring. The ESMs are connected together using ports 7 and 8. The RM monitors the
ESM bus connected to it, closes the bus if it detects an interruption and therefore
reestablishes a functioning bus configuration.
A maximum of 50 ESMs are permitted in an electrical ring. This allows a
reconfiguration time of less than 0.3 s to be achieved. The RM mode is activated
on the ESM using a DIP switch.
The maximum length of the twisted-pair cable between two ESMs is 100 m. This
means that an electrical ring including 50 ESMs can have a maximum span of 5
km.