Modbus RTU Message Format
2 Modbus® RTU Serial Communications User Manual 02/13
2. Modbus RTU Message Format
Table 2-1 Modbus RTU Message Formats
Coding system
8 bit binary
Number of data bits per
character
10 Bits
start bits - 1
data bits - 8
parity bits - 0
stop bits - 1
Parity
Not used
Bit transfer rate
300, 600, 1200, 2400, 4800, 9600, 19200, 38400 Selectable
NOTE: Not all instruments support all Baud Rates.
Duplex
Half duplex Transceiver or TX/RX
Error checking
CRC (cyclic redundancy check)
Polynomial
(CRC-16 10100000000001)
Bit transfer order
LSB first
End of message
Idle line for 3.5 or more characters (>1.82 msec for 19200).
2.1 Modbus RTU Link Layer
The link layer includes the following properties/behaviors:
Slave address recognition,
Start / End of Frame detection,
CRC-16 generation / checking,
Transmit / receive message time-out,
Buffer overflow detection,
Framing error detection,
Idle line detection.
Errors detected by the physical layer in messages received by the slave are ignored and the physical layer
automatically restarts by initiating a new receive on the next idle line detection.