Appendix B: CRC-16 Calculation
02/13 Modbus® RTU Serial Communications User Manual 27
A. Appendix: Register Map
What’s in this appendix?
This appendix describes all paramters accessible by Function Code 03, 04, 06 and 10h. Section A.1 gives
a global overview of each function and its addresses/registers. Sections A.2 through A.21 contain the
details on each function and each of its parameters.
Your particular instrument may not contain all parameters shown. If you see a function that is not on your
instrument, either it is not available for that instrument model or it is an option you did not purchase. If a
function is not available for your instrument, that will be indicated.
A.1 Register Map Overview
Table A-1describes the global register map for Function Code 03, 04, 06 and 10h. Details on each address
are in sections A.2 through A.21. Your particular instrument may not contain all functions or parameters
shown. For example, some instruments contain only one or two loops, do not contain calculated values,
setpoint programmers, etc.
Conversion of address (hex) number to register (decimal) number.
To convert the address number to the register number, convert the address from hexidecimal to decimal
and add 40001. Registers are addressed starting at zero: registers 1 – 16 are addressed as 0 – 15.
To convert the register number to the address number, subtract 40001 from the register and convert to hex.
Table A-1 Global Register Map
Start Address
(hex)
End Address
(hex)
Description See
Subsection
0000 < 0040 Miscellaneous Parameters or Loop #1 Integer A.2 or A.3
0100 013F Loop 2 and Extended Values – UDC3500 0
0040 00FF Loop #1 (floating point & bit packed) A.5
0100 013F Loop #2 Integer
0140 01FF Loop #2 (floating point & bit packed)
0240 02FF Loop #3 (floating point & bit packed)
0340 03FF Loop #4 (floating point & bit packed)
0440 04FF Loop #5 (floating point & bit packed)
0540 05FF Loop #6 (floating point & bit packed)
0640 06FF Loop #7 (floating point & bit packed)
0740 07FF Loop #8 (floating point & bit packed)
0800 081C DR4300, DR4500 Chart A.2.2
0840 08FF Loop #9 (floating point & bit packed) A.5
0940 09FF Loop #10 (floating point & bit packed)
0A40 0AFF Loop #11 (floating point & bit packed)
0B40 0BFF Loop #12 (floating point & bit packed)
0C40 0CFF Loop #13 (floating point & bit packed)
0D40 0DFF Loop #14 (floating point & bit packed)
0E40 0EFF Loop #15 (floating point & bit packed)
0F40 0FFF Loop #16 (floating point & bit packed)