Modbus RTU Function Codes
02/13 Modbus® RTU Serial Communications User Manual 9
3. Modbus RTU Function Codes
The Honeywell Universal Modbus RTU protocol uses a subset of the standard Modbus RTU function codes
to provide access to process-related information. Several MODICON function codes are employed. It is
appropriate to define instrument-specific "user-defined" function codes. Several standard Modbus RTU
function codes are supported. These standard function codes provide basic support for IEEE 32-bit floating
point numbers and 16-bit integer register representation of instrument’s process data.
Repolling of data is not supported by these instruments.
Table 3-1 Modbus RTU Function Codes Definitions
Function Code Name Usage
01 Read Coil Status Read the State of a Digital Output
02 Read Input Status Read the State of a Digital Input
03
04
Read Holding Registers /
Read Input Registers
Read Data in 16 bit Register Format (high/low). Used to
read integer or floating point process data. Registers
are consecutive and are imaged from the instrument to
the host.
05 Force Single Coil Write data to force Digital Output ON/OFF
Values of FF 00 forces DO ON
Values of 00 00 forces DO OFF
Values of FF FF releases the force of the DO
All other values are illegal and will not affect the DO.
RSX, VPR, VRX, UDC5300 ONLY
06 Preset Single Register
Write Data in 16-bit Integer Format (high/low) ONLY.
08 Loopback Test Used for diagnostic testing of the communications port.
16 (10h) Preset Multiple Registers Write Data in 16-bit Format (high/low). Used to write
integer and floating point override data. Registers
are consecutive and are imaged from the host to the
instrument.
Note: UDC will write floating point data using this
Function Code
17 (11h) Report Device ID Read instrument ID and connection information, ROM
version, etc.
20 (14h) Read General Reference Used to Read or upload the instrument’s configuration
into the host device. See Section 1.2 - Modbus RTU
Configuration Interface for a reference to the User
Manual for the specific instrument.
21 (15h) Write General Reference Used to Write or download an instrument’s
configuration into the instrument from a host device.
See Section 1.2 - Modbus RTU Configuration Interface
for a reference to the User Manual for the specific
instrument.