Appendix B: CRC-16 Calculation
38 Modbus® RTU Serial Communications User Manual 02/13
A.5 Loop Value Register Map
This table contains addresses of Loop #1; see Table A-1 on page 27 for addresses of other loops.
Address
(hex)
Register
(decimal)
Parameter Name Access Notes
0040 40065 PV R Floating Point in Engineering Units.
0042 40067 RV; Remote Set Point; SP2 R Floating Point in Engineering Units.
RSX,
VPR, VRX, UDC5300 allow writing
this value when SP2 is local (not connected)
0044 40069 Working Set Point R Floating Point in Engineering Units.
RSX, VRX,
VPR, UDC5300,: R/W
On a write to this register the instrument
will update the proper set point according to
the loop’s currently selected set point.
0046 40071 Output R/W Floating Point in Engineering Units.
UDC2500, UDC3200, UDC3500
Read Only
0048 40073 Input #1 R Floating Point in Engineering
004A 40075 Input #2 R Floating Point in Engineering Units.
004C 40077 Gain #1 (Prop Band #1 if active) R/W Floating Point
For loop #2 this cell is UDC330 Gain #3 or
UDC3500 Gain #5
004E 40079 Direction R Floating Point
0.0=Direct; 1.0=Reverse
0050 40081 Reset #1 R/W Floating Point in Repeats/Minute or
Minutes/Repeat.
For loop #2 this cell is UDC3300 Reset #3 or
UDC3500 Reset #5
0052 40083 Rate #1 R/W Floating Point in Minutes
For loop #2, this cell is UDC3300 rate #3 or
UDC3500 rate #5
0054 40085 Cycle Time #1 R/W Floating Point in Seconds.
Read-only for UDC2300, UDC3300.
For loop #2 this cell is UDC3300 Cycle Time #3
or UDC3500 Cycle Time #5
0056 40087 PV Low Range R Floating Point in Engineering Units.
0058 40089 PV High Range R Floating Point in Engineering Units.
005A 40091 Alarm #1 SP #1 R/W Floating Point in Engineering Units. Note 2
005C 40093 Alarm #1 SP #2 R/W Floating Point in Engineering Units. Note 2
005E 40095 unused
0060 40097 Gain #2 (Prop Band #2 if active) R/W Floating Point
For loop #2 this cell is UDC3300 Gain #4 or
UDC3500 Gain #6