Appendix B: CRC-16 Calculation
02/13 Modbus® RTU Serial Communications User Manual 63
A.19.1 Segment Register Map
The table below describes the registers that are part of a setpoint programmer segment. To determine the actual
register address for a parameter within a segment, add the register offset to the start address of the segment.
Register
Offset within
Segment
Parameter Name Access Notes
0 Ramp Segment R/W Bit Packed
Bit 0: 1 = ramp segment; 0=soak segment
Bit 1: 1 = guaranteed soak enabled
0 = guaranteed soak disabled
Bit 2: 1 = guaranteed soak enabled PV#2
0 = guaranteed soak disabled PV#2
Bit 0 is ignored in the hold mode.
Writing to this register is not permissible in the run
mode.
VPR, VRX ONLY
1 Events R/W Bit Packed
Bit 0: Event #1
: :
Bit 15: Event #16
0: Event OFF
1: Event ON
Writing to this register is only permissible in reset or
ready mode.
VPR, VRX ONLY
2 Time or Rate R/W Floating Point in time units configured for the set point
programmer
Writing to this register is not permissible in the run
mode.
VPR, VRX ONLY
4 Ramp or Soak value R/W Floating Point
Writing to this register is not permissible in the run
mode.
VPR, VRX ONLY
6 Soak value for auxiliary
output (use “Time or
Rate” for duration)
R/W Floating Point
Writing to this register is not permissible in the run
mode.
VPR, VRX ONLY
Comentarios a estos manuales