Appendix B: CRC-16 Calculation
02/13 Modbus® RTU Serial Communications User Manual 57
A.17 Set Point Programmer Value Register Map
Address
(hex)
Register
(decimal)
Channel Number Access Notes
1E00 47681 Set Point Programmer Output R Floating Point in Engineering Units.
1E02 47683 Current Segment Number R Floating Point; 1...Max Segment #
A write changes the segment number.
1E04 47685 Program Elapsed Time R Floating Point in Seconds -or- Time Units
Includes or runs when in Hold
Note 1, 2
1E06 47687 Program Active Time R Floating Point in Seconds -or- Time Units
Excludes or stops when in Hold
Note 1, 2
1E08 47689 Segment Time Remaining R Floating Point in Seconds -or- Time Units
1E0A 47691 Current Segment Events (Bit
Packed)
R Bit Packed
Bit 0: Event #1
:
Bit 15: Event #16
0: Event OFF
1: Event ON
Note 1, 2
1E0B 47692 Status R Bit Packed
Bit 0: 1=Ready
1: 1=Run
2: 1=Hold
3: 1=End
4: 1=Time Units in Seconds
5: 1=Time Units in Minutes
6: 1=Time Units in Hours
UDC2300, UDC2500, UDC3200,
UDC3300, UDC3500, DR4300,
DR4500,:
7: Ramp Units
0: Time
1: Rate
UDC2300, UDC2500, UDC3200,
UDC3300, UDC3500, DR4300,
DR4500,:
8: If bit 7 Set
0: EU/Hour
1: EU/Minute
Bit 9: Guaranteed Soak State
Bit 12-15: Program Selected
#1 to #4 UDC3500
1E0C 47693 Start W Signed 16 bit integer
Write to location Starts Profile;
Data ignored
Note 3