Modbus RTU Function Codes
22 Modbus® RTU Serial Communications User Manual 02/13
3.8 Function Code 17 (11h) – Report Device ID
Description
Function code 17 (11h) is used to report the Device Information that includes information like: Slave ID,
device description, and firmware version.
Query
The query message specifies the function code only.
Query message format for function code 17 (11h)
Slave
Address
Function
Code
CRC CRC
Example:
Read Device ID from a slave at address 02.
02 11 CRC CRC
Response
The response is a record format describing the instrument.
Response message format for function code 17 (11h)
Slave
Address
Function
Code
Byte
Count
Slave
ID
Run
Indicator
Status
Device
Specific
Data
CRC CRC
Slave ID – The number associated with the device.
(one byte) (byte 3)
Slave ID
(hex)
Device Type Slave ID
(hex)
Device Type
N/A DPR100 (Does not support
11h)
33 UDC3300
18 DPR180 35 UDC3500
25 DPR250 53 UDC5300, RSX, VPR, VRX
43 DR4300 02 UDC6000
45 DR4500 63 UDC6300
23 UDC2300 10 10260S
26 UDC2500 11 11280S
32 UDC3200 20 SA2001, SA2002
05 Minitrend V5, Multitrend
Plus V5
QX and SX Recorders
Run Indicator Status:
(one byte) (byte 4)
00=OFF; FF=ON