NIM Primitives
4-14
TIWAY 1 TI505 NIM User Manual
TT
= D = W
ord force (3 bytes)
MM <DDDD> where,
MM value Force state / action
00* Unforced
Forced01
MM is the forced state or forced action to take
FF** Unforce
*
word. It will not unforce a word, but it will change the word
value
If used in a Write Primitive, it can only write to an unforced
Used only in Write Primitives to unforce a word. It does
not have a DDDD value and the data length is 1 byte
instead of 3 bytes.
**
DDDD is the word value and is not used when MM=FF
Figure 6
Forced Word Data Element Format