TIWAY 1 Overview
1-5
TIWAY 1 TI505 NIM User Manual
The
TI505 NIM provides
redundant TIW
A
Y I communication ports. Each of the following
models
supports a specific type of network communication media.
PPX: Number Port A Port B
PPX:505-7339 Local Line Local Line
PPX:505-7340 RSĆ232ĆC/423 RSĆ232ĆC/423
The
RS-232-C/423 media interface is configured as Data T
erminal Equipment (DTE) and
is
used to connect the NIM to
Data Communication Equipment (DCE) for operation with
modems. This interface uses RS-423 drivers and receivers and operates at RS-423-A
signal levels (+5 or –5 volts). These levels are also RS-232-C compatible. The pin
assignments
for the RS-232-C port are given in Chapter 2.
The
Local Line interface is a differential line port for use with shielded twisted pair cable.
The Local Line interface provides line isolation and high noise immunity for
installations
up to 10,000 feet (25,000 feet depending on system loading
and baud rate
selection). The Local Line interface is recommended for applications where electrical
noise
may be a problem.
Redundancy is supported for either choice of media.